Short answer: almost any UPS for router and modem backup can power both; what separates them is how long. Choose by the runtime the manufacturer lists at a low load (around 15–25 W), make sure the outlets are battery-backed, and prefer pure sine wave output if any connected device has an active-PFC power supply.
Step 1: Measure or add up your load
Typical internet gear draws about 12–13 W combined (Ericsson and Prysmian measurements). Add any mesh node, network switch or VoIP adapter. Most setups land between 15 and 30 W.

Step 2: Read the runtime chart, not the VA
A UPS’s VA and watt ratings describe the maximum load. For a 15–30 W load, they don’t tell you much. What matters is the battery energy and the runtime at low load, which manufacturers publish in runtime charts or calculators.
If the spec sheet lists battery watt-hours, estimate: Runtime ≈ Battery Wh × efficiency ÷ Load W. If it lists only volts and amp-hours, convert first: Wh = V × Ah.
Step 3: Battery-backed vs surge-only outlets
Many UPS units have two outlet groups: some with battery backup and surge protection, others with surge protection only. Plug the modem and router into the battery side.

Step 4: Waveform
On battery, cheaper UPS models output a simulated (stepped) sine wave. Eaton notes that this may not suit devices with active Power Factor Correction (PFC) power supplies. Small modem and router adapters usually tolerate it, but a pure sine wave UPS removes the question. Details in Pure Sine Wave vs Simulated Sine Wave.
Step 5: Consider a DC mini UPS
For routers and modems only, a DC mini UPS feeds 12 V (or 9 V / 5 V) directly, skipping the inverter step. That reduces losses. Match voltage, connector size and polarity to each device’s adapter label exactly.

UPS for router setups: standard vs DC mini vs power station
| Feature | Standard UPS | DC mini UPS | Power station |
|---|---|---|---|
| Typical use | Desk, PC, network | Modem/router only | Whole essentials list |
| Switchover | Built for it | Built for it | Model-dependent |
| Losses at low load | Higher (inverter) | Lower (DC) | Lower if using DC ports |
| Battery replacement | Often user-replaceable | Varies | Usually not |
Buying checklist
- Published runtime at your load (15–30 W)
- Enough battery-backed outlets, spaced for bulky adapters
- Pure sine wave if anything has an active-PFC supply
- Replaceable battery and its expected service life
- Audible alarm that can be muted at night
Also see: How to keep Wi-Fi running during an outage.
Worked example: estimating runtime from the battery
When a maker doesn’t publish a low-load runtime, you can estimate it from the battery. The numbers below are an example to show the method, not a specific product. A UPS with a 12 V, 7 Ah battery stores about 12 × 7 = 84 Wh. At an assumed 85% conversion efficiency and a 15 W load, that is roughly 84 × 0.85 ÷ 15 ≈ 4.8 hours.
Treat that as an upper bound. Real efficiency at very light loads varies by model, and batteries lose capacity with age. The runtime chart on the maker’s spec sheet, read at your actual load, is the number to trust. If it isn’t published, ask the manufacturer before you buy a UPS for router backup.
Common mistakes when buying a UPS for router backup
- Shopping by VA rating. VA tells you the maximum load, not how long a 13 W network will run.
- Plugging the modem into a surge-only outlet, so it shuts off the moment the power fails.
- Forgetting the fiber ONT or a mesh node in another room.
- Never replacing the battery. A UPS for router use still needs a battery check every few years; follow the maker’s replacement interval.
When this doesn’t apply
- Long outages: for more than a few hours, a power station or DC battery bank usually holds far more energy than a small UPS. See how to keep Wi-Fi on during a power outage.
- Provider-supplied backup: if your phone or internet provider supplies its own battery unit for the ONT, check what it powers before adding another UPS.
FAQ
What size UPS for router and modem?
Size by runtime, not VA. Almost any small UPS handles 13–25 W; pick the one whose published runtime at that load matches the outages you expect.
Does a router need a pure sine wave UPS?
Use the rule from Step 4: choose pure sine wave if anything on the UPS has an active-PFC power supply, and check each adapter’s label or manual if you’re unsure; see pure sine wave vs simulated sine wave.
How long will a UPS run a modem and router?
Anywhere from under an hour to several hours, depending on battery size and efficiency at low load. Read the runtime chart at about 15 W.
Protecting a desktop computer too? See how to size a UPS for PC use.
Sources: Eaton; Ericsson; Prysmian. Written by Lucas, Electrical Engineer. No products were tested for this article.